Your location: HOME > Product Display  >  Transformer testing instrument
GYYC transformer on-load switch tester

The transformer on-load tap-changer tester is used to measure and analyze the electrical performance indicators of power transformers and special transformers on-load tap-changers in power systems.


Product Features

Using computer control, through a specially designed measurement circuit, the transition time, transition waveform, transition resistance, and three identical periods of the on-load tap-off switch can be measured directly by the tap-off according to needs and on-site conditions. The switch leads can also be measured by the transformer three-phase bushing and neutral point direct wiring.


Technical parameters

   1. Measurement with winding:

      Sampling method: Voltage sampling output current: DC 1A

      Transition resistance measurement range: ****0Ω-30Ω Measurement error: ±5%

      Sampling frequency: 10kHz Record transition waveform time: 0~120ms

      Measurement concurrency error: 0.1ms

    2. Measurement without winding:

      Sampling method: Current sampling output current: DC 9V Transition resistance measurement range: ****0Ω-50Ω

      Measurement error: ±5% Sampling frequency: 10kHz Recording transition waveform time: 0~120ms

      Measurement concurrency error: 0.1ms

    3. Working environment:

       Working power supply: AC 220V±10% Frequency: 50Hz±1Hz

       Use temperature: 0℃~40℃ Relative humidity: ≤85%RH


Product alias

Transformer on-load switch tester, transformer on-load tap-changer tester, on-load tap-changer tester, on-load switch tester


0.263356s