The transformer on-load tap-changer tester is used to measure and analyze the electrical performance indicators of power transformers and special transformers on-load tap-changers in power systems.
Product Features
Using computer control, through a specially designed measurement circuit, the transition time, transition waveform, transition resistance, and three identical periods of the on-load tap-off switch can be measured directly by the tap-off according to needs and on-site conditions. The switch leads can also be measured by the transformer three-phase bushing and neutral point direct wiring.
Technical parameters
1. Measurement with winding:
Sampling method: Voltage sampling output current: DC 1A
Transition resistance measurement range: ****0Ω-30Ω Measurement error: ±5%
Sampling frequency: 10kHz Record transition waveform time: 0~120ms
Measurement concurrency error: 0.1ms
2. Measurement without winding:
Sampling method: Current sampling output current: DC 9V Transition resistance measurement range: ****0Ω-50Ω
Measurement error: ±5% Sampling frequency: 10kHz Recording transition waveform time: 0~120ms
Measurement concurrency error: 0.1ms
3. Working environment:
Working power supply: AC 220V±10% Frequency: 50Hz±1Hz
Use temperature: 0℃~40℃ Relative humidity: ≤85%RH
Product alias
Transformer on-load switch tester, transformer on-load tap-changer tester, on-load tap-changer tester, on-load switch tester